Loading...
HomeMy WebLinkAboutInv# SI122859 - ROCHA CONTROLS - 07/25/2025Date Item/Description Task Number Qty.Unit Unit Price Total Price 6/25/2025 Field Tech Services: Jack Carter 45025 4 HR(S)165.00 660.00 6/25/2025 Field Tech Services: Jorge Romero 45025 8 HR(S)165.00 1,320.00 7/25/25 Troubleshot VFD 2 PowerFlex 700. Initial start testing showed an overload warning. Checked voltages and confirmed motor settings. Found phase 1 (brown) was connected to phase 2 (purple) at the motor. Swapped leads in the VFD cabinet. After swapping leads, the VFD showed a DC Bus voltage error at 705VDC, matching Pump 3 and 4. Worked with tech support for further testing. Removed motor leads and VFD ran with no faults. Reconnected leads and the same fault occurred. Tech support suggested a possible motor issue. Rocha planned to escalate the support case for verification since the motor was recently reworked. Reviewed existing system and requirements with Nate. At RIO2 and the chemical area, the ControlNet rack was communicating via ControlNet. No panel drawings were available. Upcoming equipment replacements in the area would benefit from updated drawings. RC requested existing drawings. If unavailable, drawings would need to be recreated, which would be time-consuming. In the filter area, two control boxes for four filters were scheduled for replacement. RC offered to assist and provide input. Planned to monitor for related bids. In the Main PLC 2 cabinet, the redundancy module (ControlLogix 5562) was offline. No drawings were available, and drawings were requested. Wires were running from the control panel to the Nano filter to bypass a potential conduit issue. Replacement would be quoted after the kickoff meeting. At the I-Well, a meter required replacement and control panel troubleshooting due to water ingress. Backed up and reviewed PLC and SCADA files. Workstation 1 had an active PLC software license. Backed up all PLC files. Both Workstation 1 and 2 were running GE iFix 5.1. Backed up the latest revisions. Planned future upgrades for iFix and PLCs, with RC working with Nate on scope, tag count, and estimates. Click Here to Pay Subtotal:1,980.00 Total Sales Tax:0.00 Total USD:1,980.00 Phone: Email:ar@uswatercorp.net Toll Free: Adjustments:0.00 1,980.00Amount Due: Remit To: U.S. WATER SERVICES CORPORATION 4939 CROSS BAYOU BOULEVARD NEW PORT RICHEY, FL 34652 Page: 1 Invoice Date: Invoice Number: P.O. Number Customer ID Due Date Bill To: INVOICE Job Description:RWO-2392 VFD Troubleshooting SI122859 C02611 8/24/2025 Dania Beach, FL 33004 100 W Dania Beach Boulevard City of Dania Beach New Port Richey, FL 34652 4939 Cross Bayou Blvd Rocha Controls 7/25/2025 Job Number:RWO2392 All pricing anticipates payment by check or ACH. Due to additional cost incurred, services paid by credit card will require an additional 3% processing fee. WA: