HomeMy WebLinkAboutInv# PC220711 - PC CONTROLS, INC - 06/01/2021Invoice Date 6/1/2021 Invoice # PCI220711 Bill To City of Dania Beach Accounts Payable 100 West Dania Beach Blvd Dania Beach, FL 33004 Service Location Darren Green Maintenance - Lift stations PC Controls Inc 132 NE 30th Street Wilton Manors, FL 33334 P.O. Number 2020-00000030 Terms Net 30 Due Date 7/1/2021 Technician PC/RF Comments Emergency Call Accounts not paid within 30 days of the date of the invoice are subject to a 1.5% finance charge. Phone # (954) 568-9663 Fax # (954) 563-0919 pccontrolsinc@bellsouth.net Total Due Subtotal Sales Tax (0.0%) Unit DescriptionQuantity Price Each AmountService Date Hours - Contract EC Technician - Emergency / OT5 89.00 445.005/30/2021 Troubleshoot Lift Station pumps at Lift Station # 8 - both breakers for Pumps 1 and 2 trip when soft start pulls in. Tighten 3-phase on all breakers and 120 VAC control. Clear alarms on controller and pumps run without tripping. Monitor Lift Station until station had pumped down completely and then watch several cycles. Pumps make a lot of noise/vibration and check valves barely raise possible rags in volute or check valve. $445.00 $445.00 $0.00