HomeMy WebLinkAboutInv# PCI220711 - PC CONTROLS, INC - 06/01/2021Invoice
Date
6/1/2021
Invoice #
PCI220711
Bill To
City of Dania Beach
Accounts Payable
100 West Dania Beach Blvd
Dania Beach, FL 33004
Service Location
Darren Green
Maintenance - Lift stations
PC Controls Inc
132 NE 30th Street
Wilton Manors, FL 33334
P.O. Number
2020-00000030
Terms
Net 30
Due Date
7/1/2021
Technician
PC/RF
Comments
Emergency Call
Accounts not paid within 30 days of the date of the
invoice are subject to a 1.5% finance charge.
Phone # (954) 568-9663
Fax # (954) 563-0919
pccontrolsinc@bellsouth.net
Total Due
Subtotal
Sales Tax (0.0%)
Unit DescriptionQuantity Price Each AmountService Date
Hours - Contract EC Technician - Emergency / OT5 89.00 445.005/30/2021
Troubleshoot Lift Station pumps at Lift Station #
8 - both breakers for Pumps 1 and 2 trip when
soft start pulls in. Tighten 3-phase on all
breakers and 120 VAC control. Clear alarms
on controller and pumps run without tripping.
Monitor Lift Station until station had pumped
down completely and then watch several
cycles. Pumps make a lot of noise/vibration
and check valves barely raise possible rags in
volute or check valve.
$445.00
$445.00
$0.00