Loading...
HomeMy WebLinkAboutInv# PCI220793 - PC CONTROLS, INC - 08/12/2021Invoice Date 8/12/2021 Invoice # PCI220793 Bill To City of Dania Beach Accounts Payable 100 West Dania Beach Blvd Dania Beach, FL 33004 Service Location Darren Green Maintenance - Lift stations PC Controls Inc 4114 W. Palm Aire Drive #141B Pompano Beach, FL 33069 P.O. Number 2020-00000030 Terms Net 30 Due Date 9/11/2021 Technician PC Comments Accounts not paid within 45 days of the date of the invoice are subject to a 1.5% finance charge. Phone # (954) 568-9663 Fax # TBD pccontrolsinc@bellsouth.net Total Due Subtotal Sales Tax (0.0%) Unit DescriptionQuantity Price Each AmountService Date Hours - Contract Technician8 60.00 480.008/9/2021 Install Moisture Detection and Over Temperature sensor for Pump #2 at Lift Station #6. Connect 3-phase to motor and test motor. Take amp readings - amps are 67 amps, 62 amps and 63 amps. Install Moisture Detection and Over Temperature sensor at Lift Station #4 - connect 3-phase to pump and test operation. Take amp readings. Hours - Contract Technician3 60.00 180.008/10/2021 Return to site to install DIN rail to mount sensor. Check amperage again as operation stated that the 80 amp breaker had tripped. Amp readings remain low at 54, 57 and 57 amps and full load amperage of pump is 85 amps. Lot Material - Terminals, DIN Rail and other related items. 1 28.00 28.00 $688.00 $688.00 $0.00