HomeMy WebLinkAboutInv# PCI220793 - PC CONTROLS, INC - 08/12/2021Invoice
Date
8/12/2021
Invoice #
PCI220793
Bill To
City of Dania Beach
Accounts Payable
100 West Dania Beach Blvd
Dania Beach, FL 33004
Service Location
Darren Green
Maintenance - Lift stations
PC Controls Inc
4114 W. Palm Aire Drive #141B
Pompano Beach, FL 33069
P.O. Number
2020-00000030
Terms
Net 30
Due Date
9/11/2021
Technician
PC
Comments
Accounts not paid within 45 days of the date of the
invoice are subject to a 1.5% finance charge.
Phone # (954) 568-9663
Fax # TBD
pccontrolsinc@bellsouth.net
Total Due
Subtotal
Sales Tax (0.0%)
Unit DescriptionQuantity Price Each AmountService Date
Hours - Contract Technician8 60.00 480.008/9/2021
Install Moisture Detection and Over
Temperature sensor for Pump #2 at Lift Station
#6. Connect 3-phase to motor and test motor.
Take amp readings - amps are 67 amps, 62
amps and 63 amps. Install Moisture Detection
and Over Temperature sensor at Lift Station #4
- connect 3-phase to pump and test operation.
Take amp readings.
Hours - Contract Technician3 60.00 180.008/10/2021
Return to site to install DIN rail to mount sensor.
Check amperage again as operation stated that
the 80 amp breaker had tripped. Amp readings
remain low at 54, 57 and 57 amps and full load
amperage of pump is 85 amps.
Lot Material - Terminals, DIN Rail and other related
items.
1 28.00 28.00
$688.00
$688.00
$0.00