HomeMy WebLinkAboutInv# PCI220799 - PC CONTROLS, INC - 08/16/2021Invoice Date 8/16/2021 Invoice # PCI220799 Bill To City of Dania Beach Accounts Payable 100 West Dania Beach Blvd Dania Beach, FL 33004 Service Location Darren Green Maintenance - Lift stations PC Controls Inc 4114 W. Palm Aire Drive #141B Pompano Beach, FL 33069 P.O. Number 2020-00000030 Terms Net 30 Due Date 9/15/2021 Technician PC Comments Accounts not paid within 30 days of the date of the invoice are subject to a 1.5% finance charge. Phone # (954) 568-9663 Fax # TBD pccontrolsinc@bellsouth.net Total Due Subtotal Sales Tax (0.0%) Unit DescriptionQuantity Price Each AmountService Date Hours - Contract Technician6 60.00 360.008/13/2021 Troubleshoot Lift Station #4 Pump 1. Operations state that motor starter chatters at times and blows pump breaker. Clean motor starter contacts and coil. Tighten wire on pump breaker found the downstream side of breaker terminals very loose. Check valve does not close very often and has a leak on the downstream of the check valve. Motor starting against an open check valve makes the pump start hard and could cause damage to pump. Check valve leaks all the time wether or not pump is running. Check valve only closed 2 times in 10 pump cycles. $360.00 $360.00 $0.00