HomeMy WebLinkAboutInv# PCI220799 - PC CONTROLS, INC - 08/16/2021Invoice
Date
8/16/2021
Invoice #
PCI220799
Bill To
City of Dania Beach
Accounts Payable
100 West Dania Beach Blvd
Dania Beach, FL 33004
Service Location
Darren Green
Maintenance - Lift stations
PC Controls Inc
4114 W. Palm Aire Drive #141B
Pompano Beach, FL 33069
P.O. Number
2020-00000030
Terms
Net 30
Due Date
9/15/2021
Technician
PC
Comments
Accounts not paid within 30 days of the date of the
invoice are subject to a 1.5% finance charge.
Phone # (954) 568-9663
Fax # TBD
pccontrolsinc@bellsouth.net
Total Due
Subtotal
Sales Tax (0.0%)
Unit DescriptionQuantity Price Each AmountService Date
Hours - Contract Technician6 60.00 360.008/13/2021
Troubleshoot Lift Station #4 Pump 1.
Operations state that motor starter chatters at
times and blows pump breaker. Clean motor
starter contacts and coil. Tighten wire on pump
breaker found the downstream side of breaker
terminals very loose. Check valve does not
close very often and has a leak on the
downstream of the check valve. Motor starting
against an open check valve makes the pump
start hard and could cause damage to pump.
Check valve leaks all the time wether or not
pump is running. Check valve only closed 2
times in 10 pump cycles.
$360.00
$360.00
$0.00