HomeMy WebLinkAboutInv# PCI220938 - PC CONTROLS, INC - 11/11/2021Invoice
Date
11/11/2021
Invoice #
PCI220938
Bill To
City of Dania Beach
Accounts Payable
100 West Dania Beach Blvd
Dania Beach, FL 33004
Service Location
Water Treatment Plant
Nate Costa
PC Controls Inc
4114 W. Palm Aire Drive #141B
Pompano Beach, FL 33069
P.O. Number
2019-00000043
Terms
Net 30
Due Date
12/11/2021
Technician
PC/AU
Comments
Accounts not paid within 30 days of the date of the
invoice are subject to a 1.5% finance charge.
Phone # (954) 568-9663
Fax # TBD
pccontrolsinc@bellsouth.net
Total Due
Subtotal
Sales Tax (0.0%)
Unit DescriptionQuantity Price Each AmountService Date
Hours - New Technician5 64.00 320.0011/9/2021
Hours2 - New Technician 25 32.00 160.00
Repair air leak for Plant #2 Blowdown valves.
Disconnect existing airline and run new air line
from Filter 3 and 4 Pneumatic header. Leak
test and put into service. NOTE air dryer for
compressor does not work and caused
condensation to form in compressor tank and
lines. This caused water to enter the
regulators and ruin them. One is for the
blowdown valves and the other is for Filter 4
influent valve. To pick up regulators and return
to install.
Hours - New Technician6 64.00 384.0011/10/2021
Hours2 - New Technician 26 32.00 192.00
Install new regulators on Filter #4 Influent and
on #4 Blowdown valves for Plant 2.
Troubleshoot valve actuator for Filter #3
Surface wash. Valve and valve actuator both
need replaced.
Each Regulator, Air, 1/2" NPT 75 CFM1 108.06 108.06
Each Regulator, Air, 1/4" NPT 80 CFM1 78.72 78.72
Lot Material - 1/2" Copper tubing, 1/2" Compression
fittings, TEE and other items needed for repairs
1 170.82 170.82
$1,413.60
$1,413.60
$0.00