Loading...
HomeMy WebLinkAboutInv# PCI220938 - PC CONTROLS, INC - 11/11/2021Invoice Date 11/11/2021 Invoice # PCI220938 Bill To City of Dania Beach Accounts Payable 100 West Dania Beach Blvd Dania Beach, FL 33004 Service Location Water Treatment Plant Nate Costa PC Controls Inc 4114 W. Palm Aire Drive #141B Pompano Beach, FL 33069 P.O. Number 2019-00000043 Terms Net 30 Due Date 12/11/2021 Technician PC/AU Comments Accounts not paid within 30 days of the date of the invoice are subject to a 1.5% finance charge. Phone # (954) 568-9663 Fax # TBD pccontrolsinc@bellsouth.net Total Due Subtotal Sales Tax (0.0%) Unit DescriptionQuantity Price Each AmountService Date Hours - New Technician5 64.00 320.0011/9/2021 Hours2 - New Technician 25 32.00 160.00 Repair air leak for Plant #2 Blowdown valves. Disconnect existing airline and run new air line from Filter 3 and 4 Pneumatic header. Leak test and put into service. NOTE air dryer for compressor does not work and caused condensation to form in compressor tank and lines. This caused water to enter the regulators and ruin them. One is for the blowdown valves and the other is for Filter 4 influent valve. To pick up regulators and return to install. Hours - New Technician6 64.00 384.0011/10/2021 Hours2 - New Technician 26 32.00 192.00 Install new regulators on Filter #4 Influent and on #4 Blowdown valves for Plant 2. Troubleshoot valve actuator for Filter #3 Surface wash. Valve and valve actuator both need replaced. Each Regulator, Air, 1/2" NPT 75 CFM1 108.06 108.06 Each Regulator, Air, 1/4" NPT 80 CFM1 78.72 78.72 Lot Material - 1/2" Copper tubing, 1/2" Compression fittings, TEE and other items needed for repairs 1 170.82 170.82 $1,413.60 $1,413.60 $0.00