Multiple Dates of Service - 1/21 & 24/22
Hours - Contract 2... Technician12 63.00 756.00
Hours2 - Contract ... Technician 212 32.00 384.00
1/21/2022 - Troubleshoot VFD for Skid #1 Feed
Water pump. Found bad cooling fan. Remove
VFD from electrical panel for access to cooling
fan. Replace cooling fan with one from a bad
VFD. Reinstall VFD into electrical panel and
terminate.
1/24/2022 - Test VFD operation. Cooling fan
on VFD still doesn't operate. Change START
capacitor and try again. Cooling fan still doesn't
run and neither capacitor test within their
tolerance.
$1,140.00
$1,140.00
$0.00