HomeMy WebLinkAboutInv# PCI221045 - PC CONTROLS, INC - 02/14/2022Invoice
Date
2/14/2022
Invoice #
PCI221045
Bill To
City of Dania Beach
Accounts Payable
100 West Dania Beach Blvd
Dania Beach, FL 33004
Service Location
Darren Green
Maintenance - Lift stations
PC Controls Inc
4114 W. Palm Aire Drive #141B
Pompano Beach, FL 33069
P.O. Number
2022-00000042
Terms
Net 30
Due Date
3/16/2022
Technician
PC/AU
Comments
Accounts not paid within 30 days of the date of the
invoice are subject to a 1.5% finance charge.
Phone # (954) 568-9663
Fax # TBD
pccontrolsinc@bellsouth.net
Total Due
Subtotal
Sales Tax (0.0%)
Unit DescriptionQuantity Price Each AmountService Date
Hours - Contract 2... Technician3 63.00 189.002/11/2022
Troubleshoot Lift Station 3 - neither pump runs
in HAND or AUTO. Found bad relay R1 the
fourth pole is burnt and won't conduct electricity
to the other side of that pole. Change with
another relay that doesn't use that pole. Motor
starters start now but pump #1 blows the
breaker. Meg motor - Motor is failed insulation
test shows no resistance to ground.
$189.00
$189.00
$0.00