HomeMy WebLinkAboutInv# PCI221045 - PC CONTROLS, INC - 02/14/2022Invoice Date 2/14/2022 Invoice # PCI221045 Bill To City of Dania Beach Accounts Payable 100 West Dania Beach Blvd Dania Beach, FL 33004 Service Location Darren Green Maintenance - Lift stations PC Controls Inc 4114 W. Palm Aire Drive #141B Pompano Beach, FL 33069 P.O. Number 2022-00000042 Terms Net 30 Due Date 3/16/2022 Technician PC/AU Comments Accounts not paid within 30 days of the date of the invoice are subject to a 1.5% finance charge. Phone # (954) 568-9663 Fax # TBD pccontrolsinc@bellsouth.net Total Due Subtotal Sales Tax (0.0%) Unit DescriptionQuantity Price Each AmountService Date Hours - Contract 2... Technician3 63.00 189.002/11/2022 Troubleshoot Lift Station 3 - neither pump runs in HAND or AUTO. Found bad relay R1 the fourth pole is burnt and won't conduct electricity to the other side of that pole. Change with another relay that doesn't use that pole. Motor starters start now but pump #1 blows the breaker. Meg motor - Motor is failed insulation test shows no resistance to ground. $189.00 $189.00 $0.00