HomeMy WebLinkAboutInv# PCI221161 - PC CONTROLS, INC - 05/16/2022Invoice
Date
5/16/2022
Invoice #
PCI221161
Bill To
City of Dania Beach
Accounts Payable
100 West Dania Beach Blvd
Dania Beach, FL 33004
Service Location
Darren Green
Maintenance - Lift stations
PC Controls Inc
4114 W. Palm Aire Drive #141B
Pompano Beach, FL 33069
P.O. Number
2022-00000042
Terms
Net 30
Due Date
6/15/2022
Technician
PC/AU
Comments
Accounts not paid within 30 days of the date of the
invoice are subject to a 1.5% finance charge.
Phone # (954) 568-9663
Fax # TBD
pccontrolsinc@bellsouth.net
Total Due
Subtotal
Sales Tax (0.0%)
Unit DescriptionQuantity Price Each AmountService Date
Hours - Contract 2... Technician4 63.00 252.005/13/2022
Troubleshoot Wastewater flowmeter. On arrival
the display was blank. Check 120 VAC and it
was there. Remove fuse for flowmeter coil -
test and re-install. Display works now. Perform
flow verification and certification. Site meter
read 100.5% of test meter.
Xmtr Fee - Contract Transmitter Certification Fee1 49.00 49.00
Fuel Surcharge - ... Broward and other1 10.00 10.00
$311.00
$311.00
$0.00
P.C. Controls lnc PC
CONTROLS
4114 W Palm Aire Dr 141B , Pompano Beach, FL 33069
Phone : (954) 568-9663, Fax: TBD
Ir--..J"~ E-mail: pccontrolsinc@ bellsouth.net
Certified Flow Meter Test Record
Customer: City of Dania Beach
Consumptive Use Permit #
Test Site Seahaven Marina Lift Station flowmeter District ID # ____ _
Contact Darren Green Number 954 558-2770
Meter Model Rosemount 8750WDMW Serial# 14867114
Meter Accessories: None
Pipe Information at test site
Material PVC
Outside Diameter 3.5" OD Pipe Thickness 0.3" WT
Transducer Spacing 1.475" V-Mount Distance from Meter installation is 3 feet
Test Information using Fuji Porta-Flow Portable Ultrasonic Flowmeter
Test performed @ _7.93 ______ GPM
Initial Meter Reading at Calibration Start: 438.98 X 1000 End: 439.03 X 1000 -------
50 Gallons Totalized in 376 Seconds ------Average _7.97 _ GPM
Test Meter Reading at Calibration Start: 0 X 1 End : -------49 .7 x 1
49 .7 Gallons Totalized in 376 Seconds ------Average _ 7 .93 _ GPM
Meter Tested at _I 00.5 _ % Accuracy Last Meter Test 9/19 --Last Accuracy _99 .2% _
Comments: Prior to calibration meter was reading 100.5% oftest meter -Site meter read 7 .97 GPM and
test meter read 7.93 GPM.
Performed By: NP Conaway Date: 5/13 /22
Thi s is to certify that the above listed equipment has been_s.a librated and meets or exceeds all published specifications.
Calibration was performed using sta~dards ~strum entation whose accuracy is traceable to the N .I.S .T .
Signature : N~