HomeMy WebLinkAboutInv# PCI221217 - PC CONTROLS, INC - 07/19/2022Invoice
Date
7/19/2022
Invoice #
PCI221217
Bill To
City of Dania Beach
Accounts Payable
100 West Dania Beach Blvd
Dania Beach, FL 33004
Service Location
Water Treatment Plant
Nate Costa
PC Controls Inc
4114 W. Palm Aire Drive #141B
Pompano Beach, FL 33069
P.O. Number
2022-00000042
Terms
Net 30
Due Date
8/18/2022
Technician
PC
Comments
Accounts not paid within 30 days of the date of the
invoice are subject to a 1.5% finance charge.
Phone # (954) 568-9663
Fax # TBD
pccontrolsinc@bellsouth.net
Total Due
Subtotal
Sales Tax (0.0%)
Unit DescriptionQuantity Price Each AmountService Date
Hours - Contract 2... Technician8 63.00 504.007/7/2022
Calibrate and certify Distribution Flow,
Distribution Pressure, East Supernate Flow,
Train1 Concentrate and Train2 Concentrate.
Xmtr Fee - Contract Transmitter Certification Fee5 49.00 245.00
Fuel Surcharge - ... Broward and other1 10.00 10.00
$759.00
$759.00
$0.00
PC
CONTROLS
I r--..J" C:::::
CALIBRATION CERTIFICATIONS
For
City of Dania Beach
6/22
Prepared by
P. C. CONTROLS, INC.
PC
CONTROLS
I ::r:-...J C::::
P.C. Controls Inc
4114 W Palm Aire Dr 141B, Pompano Beach, FL 33069
Phone: (954) 568-9663; Fax: TBD
E-mail: pccontrolsinc@bellsouth.net
Location : City of Dania Beach WTP
Function: East Supemate Flowmeter, Fit-123
Technician: NP Conaway
Cal. Type: Ultrasonic Comparison
Date: 717 122
DueDate: 6/23
Interval: Yearly
Test Equipment Used: FUJI Portaflow, Fluke 787
Mfr: Seametrics
Full Scale: 100 GPM
Input
47.4
47.4
Type: SCADA
Measured
Output (mA) (v)
B A
47.4
11.58
47.4
11.58
01 Full Signal in Req . Output
GPM/MGD Scale mNVolt
0 4 0
50 12 50
100 20 100
Transmitter Calibration Data
Model#: FT420
Req 'd Output
(rnA) (v)
Remarks
Serial#: 04220600
Line Size: 2"
47.4 AVG.GPM
11.58 mA
Receiver Calibration Data
Full Scale: l 00 GPM
Indication
GPM/MGD
0
50
100
Remarks
GPM
Dial X: l
This is to certify that the above listed equipment has been calibrated and meets or exceeds all published specifications.
Calibration was performed using standards and/ ·nstrumentation whose accuracy is traceable to the N.l.S.T.
Signature
PC
CONTROLS
:i: :I"'...J ~
P.C . Controls Inc
4114 W Palm Aire Dr 14 IB, Pompano Beach, FL 33069
Phone: (954) 568-9663 , Fax : TBD
E-mail: pccontrolsinc@ bellsouth.net
Certified Flow Meter Test Record
Customer: City of Dania Beach
Consumptive Use Permit# 06-00187-W
Test Site East Supernatent Flow Transmitter, FIT-123 District ID# ___ _
Contact Nate Costa Number 954 924-3616
Meter Model Seametrics FT440E Serial# 04220600
Meter Accessories: None
Pipe Information at test site
Material PVC Schedule 40
Outside Diameter 2 .375" OD Pipe Thickness .154" WT
Transducer Spacing 0.55" Z-Mount Distance from Meter installation is 10 feet
Test Information using Fuji Porta-Flow Portable Ultrasonic Flowmeter
Test performed @ __ 47.2 _____ GPM
Initial Meter Reading at Calibration Start: 8250 __ x _ 1_ End: 8650 ___ x 1
400 Gallons Totalized in 506 Seconds Average_ 4 7.4_ GPM
Test Meter Reading at Calibration Start: 0 x 1 End: 400 ___ x 1 ---
400 Gallons Totalized in 508 Seconds Average_ 47 .2 _ GPM
Meter Tested at _1004_ % Accuracy Last Meter Test 6/21 Last Accuracy_ I 01. 7% _
Comments: Prior to calibration meter was reading 90.4% oftest meter-Site meter read 41 .5 GPM and test
meter read 45.9 GPM.
Performed By: NP Conaway Date: 717/22
This is to certify that the above listed equipment has been calibrated and meets or exceeds all published specifications.
Calibration was performed using standards and/or instrumentation whose accuracy is traceable to the N.I.S .T.
Signature ~
PC
CONTROLS
I r--..:J C::::::
Location: City of Dania Beach WTP
Function: East Influent Flowmeter
Technician: NP Conaway
P.C. Controls Inc
4114 W Palm Aire Dr 14 IB, Pompano Beach, FL 33069
Phone: (954) 568-9663; Fax: TBD
E-mail: pccontrolsinc@bellsouth.net
Cal. Type: Ultrasonic Comparison
Date: 6/15/22
DueDate: 6/23
Interval: Yearly
Test Equipment Used: Fuji Portaflow, Fluke 787
Mfr: Seametrics
Full Scale: 1500 GPM
Input
0
1222
Type: SCADA
Measured
Output (mA) (v)
B A
4.00
17.10
4.00
17.0
01 Full Signal in Req . Output
GPMIMGD Scale mNVolt
0 4 0
25 8 375
50 12 750
75 16 1125
100 20 1500
Transmitter Calibration Data
Model#: FT500-22
Req 'd Output
(mA) (v)
4.00
17.0
Remarks
MA
Receiver Calibration Data
Full Scale: 1500 GPM
Indication
GPMIMGD
0
375
750
1125
1500
Remarks
GPM
Serial#: 07980639
Line Size: 16"
DialX: I
This is to certify that the above listed equipment has been calibrated and meets or exceeds all published specifications.
Calibration was performed using standards and/or instrumentation whose accuracy is traceable to the N.I.S.T.
s;gnature : ~
P.C. Controls Inc PC
CONTROLS
4114 W Palm Aire Dr l41B, Pompano Beach, FL 33069
Phone: (954) 568-9663 , Fax: TBD
I ::r--.J" C::: E-mail: pccontrolsinc@bellsouth.net
Certified Flow Meter Test Record
Customer: City of Dania Beach
Consumptive Use Permit# 06-00187-W
Test Site East Influent Flow Transmitter District ID#
Contact Nate Costa Number 954 924-3616
Meter Model Seametrics FT440-W Serial# 1011805
Meter Accessories: None
Pipe Information at test site
Material Ductile Iron Schedule 53
Outside Diameter 17.4" OD Pipe Thickness 0.43" WT
Transducer Spacing 13.52" V-Mount Distance from Meter installation is 20 feet
Test Information using Fuji Porta-Flow Portable Ultrasonic Flowmeter
Test performed @ __ 1208 _____ GPM
Initial Meter Reading at Calibration Start: 875200 X 1 End: 887200 -----x l
__ 12,000 __ Gallons Totalized in _589 __ Seconds Average _1222.4_ GPM
Test Meter Reading at Calibration Start : 0 x 1 ---End: 12000 X 1
__ 12,000 __ Gallons Totalized in _596 __ Seconds Average _1208.1_ GPM
Meter Tested at _ l 01.2 _ % Accuracy Last Meter Test N I A Last Accuracy __ _
Comments: Prior to calibration meter was reading 101.2% of test meter -Site meter read 1222.4 GPM and
test meter read 1208. l GPM.
Performed By: NP Conaway Date: 6115 /22
This is to certify that the above listed equipment has been calibrated and meets or exceeds all published specifications .
Calibration was performed using standards and /or instru tation whose accuracy is traceable to the N.l.S .T.
Signature
PC P.C. Controls Inc
CONTROLS
4114 W Palm Aire Dr 14 IB, Pompano Beach, FL 33069
Phone: (954) 568-9663; Fax: TBD
I r--..T C::. E-mail: pccontrolsinc@bellsouth.net
Location: City of Dania Beach WTP
Function: Influent to Membranes tlowmeter, FIT-1020
Technician: NP Conaway
Cal. Type: Ultrasonic Comparison
Date: 6/15/22
DueDate: 6/23
Interval: Yearly
Test Equipment Used: FUJI Portraflow, Fluke 787, Hart 475
Mfr: Rosemount
Full Scale: 2000 GPM
Input
771
771
4.00 mA
20 .00mA
Type: SCADA
Measured
Output (mA) (v)
B A
771 771
10.16 10 .16
4.00 4.00
20.00 20.00
01 Full Signal in Req. Output
GPM/MGD Scale mANolt
0 4 0
50 12 1000
100 20 2000
Transmitter Calibration Data
Model#: 8750WA
Req 'd Output
(mA) (v)
Remarks
Serial#: 0011439
Line Size: 1 O"
771 AVG.GPM
10 .16 mA
4.00
20.00
Receiver Calibration Data
Full Scale: 2000 GPM
Indication
GPM/MGD
0
1000
2000
Remarks
GPM
Dial X: 1
This is to certify that the above listed equipment has been calibrated and meets or exceeds all published specifications.
Calibration was performed using stand~~mentation whose accuracy is traceable to the N .I.S.T.
Signature : ~' -
PC
CONTROLS
II:-...J"~
P.C . Controls Inc
4114 W Palm Aire Dr 141 B, Pompano Beach , FL 33069
Phone: (954) 568-9663 , Fax: TBD
E-mail : pccontrolsinc @bellsouth .net
Certified Flow Meter Test Record
Customer: City of Dania Beach
Consumptive Use Permit # 06-00187-W
Test Site Influent to Membranes Flow transmitter, FIT-1929 District ID #_
Contact Nate Costa Number 954 924-3616
Meter Model Rosemount 8750W A Serial # 0011439
Meter Accessories: Mag
Pipe Information at test site
Material
Outside Diameter .11.J..'..'. 0 D Pipe Thickness 1.0" WT
Transducer Spacing 7.737" V-Mount Distance from Meter installation is 5 feet
Test Information using Fuji Porta-Flow Portable Ultrasonic Flowmeter
Test performed @_754 ______ GPM
Initial Meter Reading at Calibration Start: 39585200 X 1 End: 39585904 X I ---------
__ 7,904 __ Gallons Totalized in _615 __ Seconds Average _771 .1_ GPM
Test Meter Reading at Calibration Start: __ O __ X_l _ End: __ 8000 __ X_l __
8,000 __ Gallons Totalized in _636 __ Seconds Average _754.l _ GPM
Meter Tested at _ l 02.3 _ % Accuracy Last Meter Test 6/21 Last Accuracy_99 .9%_
Comments: Prior to calibration meter was reading 102.3% of test meter -Site meter read 771 . l GPM and
test meter read 754 . l GPM.
Performed By: NP Conaway Date: 6/15 /22
This is to certify that th e above li sted equipment has been calibrated and meets or exceeds all publi shed specifi cation s.
Calibration was performed usi ng standards and/or instru tion whose accuracy is traceable to the N .I.S .T.
Signature
P.C. Controls Inc PC
CONTROLS
4114 W Palm Aire Dr 141B, Pompano Beach, FL 33069
Phone: (954) 568-9663; Fax: TBD
:c:r:....:rc::::: E-mail: pccontrolsinc@bellsouth.net
Location: City of Dania Beach WTP
Function: RO Train 1 Concentrate flowmeter
Technician: NP Conaway
Test Equipment Used: FUJI Portaflow, Fluke 787, Hart 475
Cal. Type: Ultrasonic Comparison
Date: 717/22
DueDate: 6/23
Interval: Yearly
Mfr: Rosemount
Transmitter Calibration Data
Model#: 8750WA Serial#: 0010681
Line Size: 8" Full Scale: 150 GPM
Input
0
0
4.00mA
20.00 mA
Type: SCADA
Measured
Output (mA) (v)
B A
0 0
4.00 4.00
4.00 4.00
20.02 20.00
01 Full Signal in Req. Output
GPM/MGD Scale mA/Volt
0 4 0
50 12 75
100 20 150
Req 'd Output
(mA) (v)
Remarks
0 AVG.GPM
4.00 mA
4.00
20.00
Receiver Calibration Data
Full Scale: 150 GPM
Indication
GPM/MGD
0
75
150
Remarks
GPM
Dial X: 1
This is to certify that the above listed equipment has been calibrated and meets or exceeds all published specifications.
Calibration w~ P'<fnrmOO o<ing <tand"d; ~df~ntatfon who~ ~'uracy i• •~eoblo to tho N .I.S.T.
Signature : ~
PC
CONTROLS
I J:"-..J" C::::
P.C . Controls Inc
4114 W Palm Aire Dr 141B, Pompano Beach, FL 33069
Phone: (954) 568-9663, Fax: TBD
E-mail: pccontrolsinc@ bellsouth.net
Certified Flow Meter Test Record
Customer: City of Dania Beach
Consumptive Use Permit # 06-00187-W
Test Site Train I Concentrate Flow transmitter, FIT-3165 District ID#
Contact Nate Costa Number 954 924-3616
Meter Model Rosemount 8750W Serial# 0010681
Meter Accessories: Mag
Pipe Information at test site
Material Stainless Steel Schedule 10
Outside Diameter 3 .50" OD Pipe Thickness 0.120" WT
Transducer Spacing 5 .72" V-Mount Distance from Meter installation is 20 Feet
Test Information using Fuji Porta-Flow Portable Ultrasonic Flowmeter
Test performed @ __ 76.2 _____ GPM
Initial Meter Reading at Calibration Start: 101 791500 X 1 End: 101792289 x 1 -------
789 Gallons Totalized in 615 Seconds ------Average _77.0_ GPM
Test Meter Reading at Calibration Start: 0 X 1 End : ------785 x 1
785 Gallons Totalized in 618 ---Seconds Average _ 76.2_ GPM
Meter Tested at _101.0_ % Accuracy Last Meter Test 6/21 Last Accuracy_96.6%_
Comments: Prior to calibration meter was reading 101% oftest meter -Site meter read 77.0 GPM and test
meter read 76.2 GPM.
Performed By: NP Conaway Date: 7 /7 /22
This is to certi fy that the above li sted equipment has been calibrated and meets or exceeds all published specifications .
Calibration was performed using standards and/or instru ation whose accuracy is traceable to the N .I.S .T.
Signature
PC P.C . Controls Inc
CONTROLS
4114 W Palm Aire Dr 141B , Pompano Beach, FL 33069
Phone: (954) 568-9663; Fax : TBD
Ir.....:JC:: E-mail: pccontrolsinc@ bellsouth.net
Location: City of Dania Beach WTP
Function : RO Train 2 Concentrate tlowmeter, FIT-3265
Technician: NP Conaway
Cal. Type: Ultrasonic Comparison
Date: 717/22
DueDate: 6/23
Interval: Yearly
Test Equipment Used: FUJI Portaflow, Fluke 787, Hart 475
Mfr: Rosemount
Full Scale: 150 GPM
Input
76.2
76.2
4.00 mA
20.00 mA
Type: SCADA
Measured
Output (mA) (v)
B A
76.2 76.2
12.12 12.12
4.00 4.00
20.00 20.00
01 Full Signal in Req. Output
GPM/MGD Scale mANolt
0 4 0
50 12 75
100 20 150
Transmitter Calibration Data
Model#: 8750WA
Req 'd Output
(mA) (v)
Remark s
Serial#: 0010682
Line Size : 8"
76.2 AVG.GPM
12.12 mA
4.00
20.00
Receiver Calibration Data
Full Scale: 150 GPM
Indication
GPM/MGD
0
75
150
Remarks
GPM
Dial X: 1
This is to certify that the above listed equipment has been calibrated and meets or exceeds all published s pecifications .
Calibration was performed using standards an7entation whose accuracy is traceable to the N.I.S.T.
Signature : ~
PC
CONTROLS
J: r--..J" c:::::
P.C. Controls Inc
4114 W Palm Aire Dr 14 lB, Pompano Beach, FL 33069
Phone: (954) 568-9663, Fax: TBD
E-mail: pccontrolsinc@bellsouth.net
Certified Flow Meter Test Record
Customer: City of Dania Beach
Consumptive Use Permit# 06-00187-W
Test Site Train 2 Concentrate Flow transmitter, FTT-3265 District ID#
Contact Nate Costa Number 954 924-3616
Meter Model Rosemount 8750W A Serial# 0010682
Meter Accessories: Mag
Pipe Information at test site
Material PVC Schedule 80
Outside Diameter 8.625" OD Pipe Thickness 0.5'' WT
Transducer Spacing 5.72" V-Mount Distance from Meter installation is 20 Feet
Test Information using Fuji Porta-Flow Portable Ultrasonic Flowmeter
Test performed @ _76.2 ______ GPM
Initial Meter Reading at Calibration Start: _7802912_X _l_ End: _7803712 __ X_J __
800 ___ Gallons Totalized in _ 622 __ Seconds Average _ 77.2_ GPM
Test Meter Reading at Calibration Start : 0 X 1 End: 800 X 1 -------
800 Gallons Totalized in 630 ----Seconds Average _ 76.2_ GPM
Meter Tested at _101.3_ % Accuracy Last Meter Test 6/21 Last Accuracy_lOl .3%_
Comments: Prior to calibration meter was reading 101.3% oftest meter-Site meter read 77.2 GPM and test
meter read 76.2 GPM.
Performed By: NP Conaway Date: 717/22
This is to certify that the above li sted equipment has been calibrated and meets or exceeds all published specifications.
C"1 ibratio::::rm<d u•ing '"°'7trum~brtiou who" •reuraoy fa trare•hl< to the N.L.S .T.
P.C. Controls Inc PC
CONTROLS
4114 W Palm Aire Dr 141B, Pompano Beach, FL 33069
Phone: (954) 568-9663 ; Fax: TBD
I r--..J C:::: E-mail: pccontrolsinc@bellsouth.net
Location: City of Dania Beach WTP
Function: High Service Effluent Flow Transmitter
Technician: NP Conaway
Cal. Type: Pressure
Date: 717 122
DueDate: 6/23
Interval: Yearly
Test Equipment Used: Fluke 717, Fluke 787
Transmitter Calibration Data
Mfr: ABB Model#: 264DSGSSB I H
Full Scale: 6000 GPM@ 107.56" H20
Measured Req 'd Output
Input Output (mA) (v) (mA) (v)
B A Remarks
O" 4.02
53.78" 15.33
107.56" 20.02
4.00 mA 4.00
20.00mA 20.00
Type: SCADA
01 Full Signal in
Scale mA/Volt
0 4
25 8
50 12
75 16
100 20
4.00
15.31
20.00
4.00
20.00
Req . Output
GPM/MGD
0.0
1500.0
3000.0
4500.0
6000.0
4.00 MA
15.31
20.00
4.00
20.000
Receiver Calibration Data
Full Scale: 6000 GPM
Indication
GPM/MGD
0.5
1500.3
3000.2
4500.2
6000.4
Remarks
GPM
Serial#: 6407008756
Line Size:
DialX: 1
This is to certify that the above listed equipment has been calibrated and meets or exceeds all published s pecifications.
Calibration was performed using standards and/or i mentation whose accuracy is traceable to the N .l.S .T.
Signature
P.C. Controls Inc PC
CONTROLS
4114 W Palm Aire Dr 141 B , Pompano Beach, FL 33069
Phone: (954) 568-9663; Fax: TBD
:c::r:---..:rc:::: E-mail: pccontrolsinc@ bellsouth.net
Location: City of Dania Beach WTP
Function: High Service Effluent Pressure Transmitter
Technician: NP Conaway
Cal. Type: Pressure
Date: 7 /7 /22
DueDate: 6 /23
Interval: Yearly
Test Equipment Used: Fluke 717, Fluke 787
Mfr: ABB
Full Scale: 348 PSI
lnput
0
87
174
361
348
Type: SCADA
Measured
Output (mA) (v)
B A
4.01
8.00
12.00
16.00
-
4.00
8.00
12.00
16.00
-
01 Full Signal in Req . Output
GPM/MGD Scale mAfVolt
0 4 0.0
25 8 87.0
50 12 174.0
75 16 261.0
100 20 348.0
Transmitter Calibration Data
Model#: 2600T
Req 'd Output
(mA) (v)
4.00
8.00
12.00
16.00
20.00
Remarks
Receiver Calibration Data
Full Scale: 348 PSI
Indication
GPM/MGD
0.0
87.0
174.0
261.0
348.0
Remarks
PSI
Serial#: 6407008757
Line Size:
DialX: I
This is to certify that the above listed equipment has been calibrated and meets or exceeds all publi shed specifications.
Calibration was performed using standards and/or inst ntation whose accuracy is traceable to the N .I.S .T.
Signature