HomeMy WebLinkAboutInv# PCI221233 - PC CONTROLS, INC - 08/08/2022Invoice Date 8/8/2022 Invoice # PCI221233 Bill To City of Dania Beach Accounts Payable 100 West Dania Beach Blvd Dania Beach, FL 33004 Service Location Darren Green Maintenance - Lift stations PC Controls Inc 4114 W. Palm Aire Drive #141B Pompano Beach, FL 33069 P.O. Number 2022-00000042 Terms Net 30 Due Date 9/7/2022 Technician PC Comments Accounts not paid within 30 days of the date of the invoice are subject to a 1.5% finance charge. Phone # (954) 568-9663 Fax # TBD pccontrolsinc@bellsouth.net Total Due Subtotal Sales Tax (0.0%) Unit DescriptionQuantity Price Each AmountService Date Hours - Contract 2... Technician4 63.00 252.008/1/2022 Hours2 - Contract ... Technician 24 32.00 128.00 Troubleshoot Lift Station #2 Motor Starter for Pump2 - had caught fire. Remove burnt wires and cap off. Cut out burnt sections of wire and but splice. Meg motor for pump. Motor megs bad. Power up control panel and power Pump #2. Test operation of Pump2. Pump trips thermal overloads even though amperage is not high. Recommend to replace motor starter for Pump2 with new melting alloy overload and thermal overloads. Motor needs to be pulled and repaired. Also suggest that electronic overloads on Pump1 also be replaced with new melting alloy thermal overload relay and thermals. Lot Material - misc1 5.00 5.00 Fuel Surcharge - ... Broward and other1 10.00 10.00 $395.00 $395.00 $0.00