Hours2 - Contract ... Technician 24 32.00 128.00
Troubleshoot Lift Station #2 Motor Starter for
Pump2 - had caught fire. Remove burnt wires
and cap off. Cut out burnt sections of wire and
but splice. Meg motor for pump. Motor megs
bad. Power up control panel and power Pump
#2. Test operation of Pump2. Pump trips
thermal overloads even though amperage is not
high. Recommend to replace motor starter for
Pump2 with new melting alloy overload and
thermal overloads. Motor needs to be pulled
and repaired. Also suggest that electronic
overloads on Pump1 also be replaced with new
melting alloy thermal overload relay and
thermals.
Lot Material - misc1 5.00 5.00