Loading...
HomeMy WebLinkAboutInv# PCI221224 - PC CONTROLS, INC - 07/20/2022Invoice Date 7/20/2022 Invoice # PCI221224 Bill To City of Dania Beach Accounts Payable 100 West Dania Beach Blvd Dania Beach, FL 33004 Service Location Darren Green Maintenance - Lift stations PC Controls Inc 4114 W. Palm Aire Drive #141B Pompano Beach, FL 33069 P.O. Number 2022-00000042 Terms Net 30 Due Date 8/19/2022 Technician PC Comments Accounts not paid within 30 days of the date of the invoice are subject to a 1.5% finance charge. Phone # (954) 568-9663 Fax # TBD pccontrolsinc@bellsouth.net Total Due Subtotal Sales Tax (0.0%) Unit DescriptionQuantity Price Each AmountService Date Hours - Contract 2... Technician3 63.00 189.007/19/2022 Troubleshoot Lift Station 16. Operations state that if they disconnect Pump 1 for repair - Pump 2 won't run. Found Pumps 1 and 2 cross-wired so when Pump 1 is disconnected Pump 2 is disabled because of Thermal Switch being disconnected on Pump 2. Correct wiring and test through several cycles. Fuel Surcharge - ... Broward and other1 10.00 10.00 $199.00 $199.00 $0.00