HomeMy WebLinkAboutInv# PCI221302 - PC CONTROLS, INC - 09/30/2022Invoice
Date
9/30/2022
Invoice #
PCI221302
Bill To
City of Dania Beach
Accounts Payable
100 West Dania Beach Blvd
Dania Beach, FL 33004
Service Location
Water Treatment Plant
Nate Costa
PC Controls Inc
4114 W. Palm Aire Drive #141B
Pompano Beach, FL 33069
P.O. Number
2022-00000042
Terms
Net 30
Due Date
10/30/2022
Technician
JES
Comments
Emergency Call
Accounts not paid within 30 days of the date of the
invoice are subject to a 1.5% finance charge.
Phone # (954) 568-9663
Fax # TBD
pccontrolsinc@bellsouth.net
Total Due
Subtotal
Sales Tax (0.0%)
Unit DescriptionQuantity Price Each AmountService Date
Hours - Contract 2... Technician 63.00 63.009/30/2022
Hours2 - Contract ... Technician 2 32.00 32.00
Troubleshoot High Service Pump 2 VFD and
motor. VFD has an error code "over voltage".
Disconnect motor at VFD and test VFD. VFD
runs without error code and output voltage is
stable and balanced. Meg motor from VFD.
The motor megs bad. Open junction box on
motor and disconnect motor and meg the motor
eliminating underground cabling. Motor megs
bad again. Motor is bad and VFD is good.
Remove junction box and cabling from motor.
Motor is ready for removal and repair.
Fuel Surcharge - ... Broward and other1 10.00 10.00
$105.00
$105.00
$0.00