Loading...
HomeMy WebLinkAboutInv# PCI221302 - PC CONTROLS, INC - 09/30/2022Invoice Date 9/30/2022 Invoice # PCI221302 Bill To City of Dania Beach Accounts Payable 100 West Dania Beach Blvd Dania Beach, FL 33004 Service Location Water Treatment Plant Nate Costa PC Controls Inc 4114 W. Palm Aire Drive #141B Pompano Beach, FL 33069 P.O. Number 2022-00000042 Terms Net 30 Due Date 10/30/2022 Technician JES Comments Emergency Call Accounts not paid within 30 days of the date of the invoice are subject to a 1.5% finance charge. Phone # (954) 568-9663 Fax # TBD pccontrolsinc@bellsouth.net Total Due Subtotal Sales Tax (0.0%) Unit DescriptionQuantity Price Each AmountService Date Hours - Contract 2... Technician 63.00 63.009/30/2022 Hours2 - Contract ... Technician 2 32.00 32.00 Troubleshoot High Service Pump 2 VFD and motor. VFD has an error code "over voltage". Disconnect motor at VFD and test VFD. VFD runs without error code and output voltage is stable and balanced. Meg motor from VFD. The motor megs bad. Open junction box on motor and disconnect motor and meg the motor eliminating underground cabling. Motor megs bad again. Motor is bad and VFD is good. Remove junction box and cabling from motor. Motor is ready for removal and repair. Fuel Surcharge - ... Broward and other1 10.00 10.00 $105.00 $105.00 $0.00