HomeMy WebLinkAboutInv# PCI221343 - PC CONTROLS, INC - 11/16/2022Invoice
Date
11/16/2022
Invoice #
PCI221343
Bill To
City of Dania Beach
Accounts Payable
100 West Dania Beach Blvd
Dania Beach, FL 33004
Service Location
Water Treatment Plant
Nate Costa
PC Controls Inc
4114 W. Palm Aire Drive #141B
Pompano Beach, FL 33069
P.O. Number
230157
Terms
Net 30
Due Date
12/16/2022
Technician
PC/DD
Comments
Accounts not paid within 30 days of the date of the
invoice are subject to a 1.5% finance charge.
Phone # (954) 568-9663
Fax # TBD
pccontrolsinc@bellsouth.net
Total Due
Subtotal
Sales Tax (0.0%)
Unit DescriptionQuantity Price Each AmountService Date
Hours - Contract 2... Technician8 63.00 504.0011/10/2022
Hours - Contract 2... Technician8 63.00 504.00
Troubleshoot High Service Pump #3 - pump
and VFD. Disconnected VFD output to motor
and meg motor from VFD. Motor megs bad.
Disconnect motor and meg motor eliminating
underground wiring. Motor megs bad. Run
VFD with motor disconnected. Output has
voltage and ramps to full speed. VFD is ok.
Troubleshoot Supernate flowmeter. Clean
screen in Y strainer screen. Remove flowmeter
and clean. Run pump with flowmeter and Y
strainer removed from pump to flush pipe of
debris. Re-install flowmeter and Y strainer
screen and close cap. Flowmeter works in
HAND but does not run in AUTO. Found Main
breaker for Supernate pump tripped. Reset
breaker and test and put into service. Install
new pilot solenoid valve on Filter #4 Influent
valve. Test drive and put into service.
Pneumatic Influent valve full of water so we
cycled valve several times to remove water.
Fuel Surcharge - ... Broward and other1 10.00 10.00
$1,018.00
$1,018.00
$0.00