Loading...
HomeMy WebLinkAboutInv# PCI221343 - PC CONTROLS, INC - 11/16/2022Invoice Date 11/16/2022 Invoice # PCI221343 Bill To City of Dania Beach Accounts Payable 100 West Dania Beach Blvd Dania Beach, FL 33004 Service Location Water Treatment Plant Nate Costa PC Controls Inc 4114 W. Palm Aire Drive #141B Pompano Beach, FL 33069 P.O. Number 230157 Terms Net 30 Due Date 12/16/2022 Technician PC/DD Comments Accounts not paid within 30 days of the date of the invoice are subject to a 1.5% finance charge. Phone # (954) 568-9663 Fax # TBD pccontrolsinc@bellsouth.net Total Due Subtotal Sales Tax (0.0%) Unit DescriptionQuantity Price Each AmountService Date Hours - Contract 2... Technician8 63.00 504.0011/10/2022 Hours - Contract 2... Technician8 63.00 504.00 Troubleshoot High Service Pump #3 - pump and VFD. Disconnected VFD output to motor and meg motor from VFD. Motor megs bad. Disconnect motor and meg motor eliminating underground wiring. Motor megs bad. Run VFD with motor disconnected. Output has voltage and ramps to full speed. VFD is ok. Troubleshoot Supernate flowmeter. Clean screen in Y strainer screen. Remove flowmeter and clean. Run pump with flowmeter and Y strainer removed from pump to flush pipe of debris. Re-install flowmeter and Y strainer screen and close cap. Flowmeter works in HAND but does not run in AUTO. Found Main breaker for Supernate pump tripped. Reset breaker and test and put into service. Install new pilot solenoid valve on Filter #4 Influent valve. Test drive and put into service. Pneumatic Influent valve full of water so we cycled valve several times to remove water. Fuel Surcharge - ... Broward and other1 10.00 10.00 $1,018.00 $1,018.00 $0.00