Loading...
HomeMy WebLinkAboutInv# PCI221252 - PC CONTROLS, INC - 08/17/2022Invoice Date 8/17/2022 Invoice # PCI221252 Bill To City of Dania Beach Accounts Payable 100 West Dania Beach Blvd Dania Beach, FL 33004 Service Location Darren Green Maintenance - Lift stations PC Controls Inc 4114 W. Palm Aire Drive #141B Pompano Beach, FL 33069 P.O. Number 2022-00000042 Terms Net 30 Due Date 9/16/2022 Technician PC/DD Comments Emergency Call Accounts not paid within 30 days of the date of the invoice are subject to a 1.5% finance charge. Phone # (954) 568-9663 Fax # TBD pccontrolsinc@bellsouth.net Total Due Subtotal Sales Tax (0.0%) Unit DescriptionQuantity Price Each AmountService Date Hours - Contract 2... Technician5 63.00 315.008/16/2022 Hours2 - Contract ... Technician 25 32.00 160.00 Troubleshoot Pump #2 at Lift Station at Beach Marina. Found potential relay chattering. Switch potential relay from Pump #1 to Pump #2. Check START and RUN capacitor with meter. Tighten capacitor connections. Pump trips on overload because of to much debris in Wet Well. Pull pump and run in a bucket of water to prove pump is a good. Pump ran for over a half hour in bucket. Call for a VAC truck but when it arrived it couldn't reach Wet Well. Pump will continue to trip until debris removed from Wet Well. Fuel Surcharge - ... Broward and other1 10.00 10.00 $485.00 $485.00 $0.00