Hours - Contract 2... Technician5 63.00 315.008/16/2022
Hours2 - Contract ... Technician 25 32.00 160.00
Troubleshoot Pump #2 at Lift Station at Beach
Marina. Found potential relay chattering.
Switch potential relay from Pump #1 to Pump
#2. Check START and RUN capacitor with
meter. Tighten capacitor connections. Pump
trips on overload because of to much debris in
Wet Well. Pull pump and run in a bucket of
water to prove pump is a good. Pump ran for
over a half hour in bucket. Call for a VAC truck
but when it arrived it couldn't reach Wet Well.
Pump will continue to trip until debris removed
from Wet Well.