Loading...
HomeMy WebLinkAboutInv# PCI221396 - PC CONTROLS, INC - 01/10/2023Invoice Date 1/10/2023 Invoice # PCI221396 Bill To City of Dania Beach Accounts Payable 100 West Dania Beach Blvd Dania Beach, FL 33004 Service Location Darren Green Maintenance - Lift stations PC Controls Inc 4114 W. Palm Aire Drive #141B Pompano Beach, FL 33069 P.O. Number 230157 Terms Net 30 Due Date 2/9/2023 Technician PC/DD Comments Accounts not paid within 30 days of the date of the invoice are subject to a 1.5% finance charge. Phone # (954) 568-9663 Fax # TBD pccontrolsinc@bellsouth.net Total Due Subtotal Sales Tax (0.0%) Unit DescriptionQuantity Price Each AmountService Date Hours - Contract Technician5 69.00 345.001/6/2023 Hours2 - Contract Technician 25 35.00 175.00 Troubleshoot Lift Station 8 Pump #2, pump would not run in HAND or AUTO. We Found a bad Phase Monitor PM2 and replaced it with a new Phase Monitor (site provided). We then tested the pumps and put into service. Troubleshoot Lift Station 9 Pump #2. Pump runs in HAND but will not run in AUTO. Clear alarms on Multi-Smart controller. Pump still will not run in AUTO. Found other hidden fault for Over-Amperage, reset alarm and pump now runs in AUTO and HAND. Check operation through 2 cycles and put into service. Fuel Surcharge - ... Broward and other1 10.00 10.00 $530.00 $530.00 $0.00