Hours2 - Contract Technician 25 35.00 175.00
Troubleshoot Lift Station 8 Pump #2, pump
would not run in HAND or AUTO. We Found a
bad Phase Monitor PM2 and replaced it with a
new Phase Monitor (site provided). We then
tested the pumps and put into service.
Troubleshoot Lift Station 9 Pump #2. Pump
runs in HAND but will not run in AUTO. Clear
alarms on Multi-Smart controller. Pump still will
not run in AUTO. Found other hidden fault for
Over-Amperage, reset alarm and pump now
runs in AUTO and HAND. Check operation
through 2 cycles and put into service.
Fuel Surcharge - ... Broward and other1 10.00 10.00