Unit DescriptionQuantity Price Each AmountService Date
Hours - Contract Technician8 69.00 552.002/8/2023
Hours2 - Contract Technician 28 35.00 280.00
Troubleshoot Lift Station 4 - operator says
pump cycle blows breaker occasionally and
new level control seemed to not be working
correctly. Found Submersible level transmitter
tangled with Low Level float. Untangle and
move Low Level float to different hook. Level
transmitter was being lifted up by the float.
Take amp readings on both pumps. Pump #1
was borderline pulling 54-63 amps. Pump # 2
was over thermal rating of 65 amps reading
68-69 amps. Tighten all connections for pump
at the breakers and motor starter. Take amp
readings all amperages are now reading below
65 amp rating of thermal. Troubleshoot pump
#2 at Lift Station 8. Pump won't run is the
complaint. Found thermal switch light on for
pump. Bypass thermal switch and try pump in
HAND. Pump blows pump breaker as well as
panel Main breaker. Meg motor - motor is
shorted to ground and needs rewound or
replaced.