HomeMy WebLinkAboutInv# PCI221431 - PC CONTROLS, INC - 02/09/2023Invoice Date 2/9/2023 Invoice # PCI221431 Bill To City of Dania Beach Accounts Payable 100 West Dania Beach Blvd Dania Beach, FL 33004 Service Location Darren Green Maintenance - Lift stations PC Controls Inc 4114 W. Palm Aire Drive #141B Pompano Beach, FL 33069 P.O. Number 230157 Terms Net 30 Due Date 3/11/2023 Technician PC/DD Comments Accounts not paid within 30 days of the date of the invoice are subject to a 1.5% finance charge. Phone # (954) 568-9663 Fax # TBD pccontrolsinc@bellsouth.net Total Due Subtotal Sales Tax (0.0%) Unit DescriptionQuantity Price Each AmountService Date Hours - Contract Technician8 69.00 552.002/8/2023 Hours2 - Contract Technician 28 35.00 280.00 Troubleshoot Lift Station 4 - operator says pump cycle blows breaker occasionally and new level control seemed to not be working correctly. Found Submersible level transmitter tangled with Low Level float. Untangle and move Low Level float to different hook. Level transmitter was being lifted up by the float. Take amp readings on both pumps. Pump #1 was borderline pulling 54-63 amps. Pump # 2 was over thermal rating of 65 amps reading 68-69 amps. Tighten all connections for pump at the breakers and motor starter. Take amp readings all amperages are now reading below 65 amp rating of thermal. Troubleshoot pump #2 at Lift Station 8. Pump won't run is the complaint. Found thermal switch light on for pump. Bypass thermal switch and try pump in HAND. Pump blows pump breaker as well as panel Main breaker. Meg motor - motor is shorted to ground and needs rewound or replaced. Fuel Surcharge - ... Broward and other1 10.00 10.00 $842.00 $842.00 $0.00