HomeMy WebLinkAboutInv# PCI221518 - PC CONTROLS, INC - 04/18/2023Invoice
Date
4/18/2023
Invoice #
PCI221518
Bill To
City of Dania Beach
Accounts Payable
100 West Dania Beach Blvd
Dania Beach, FL 33004
Service Location
Water Treatment Plant
Nate Costa
PC Controls Inc
4114 W. Palm Aire Drive #141B
Pompano Beach, FL 33069
P.O. Number
230157
Terms
Net 30
Due Date
5/18/2023
Technician
PC/DD
Comments
Accounts not paid within 30 days of the date of the
invoice are subject to a 1.5% finance charge.
Phone # (954) 568-9663
Fax # TBD
pccontrolsinc@bellsouth.net
Total Due
Subtotal
Sales Tax (0.0%)
Unit DescriptionQuantity Price Each AmountService Date
Hours - Contract Technician3 69.00 207.004/17/2023
Hours2 - Contract Technician 23 35.00 105.00
Troubleshoot High Service Pump 2, Ran the
VFD, also megged the VFD to ensure proper
voltage output and it worked fine, we then
disconnected motor and troubleshot wires from
motor itself. Megged the wires from the motor
itself and the output was not sufficient deeming
the motor being bad.
Fuel Surcharge - ... Broward and other1 10.00 10.00
$322.00
$322.00
$0.00