Loading...
HomeMy WebLinkAboutInv# PCI221545 - PC CONTROLS, INC - 05/23/2023Invoice Date 5/23/2023 Invoice # PCI221545 Bill To City of Dania Beach Accounts Payable 100 West Dania Beach Blvd Dania Beach, FL 33004 Service Location Darren Green Maintenance - Lift stations PC Controls Inc 4114 W. Palm Aire Drive #141B Pompano Beach, FL 33069 P.O. Number 230157 Terms Net 30 Due Date 6/22/2023 Technician PC/DE Comments Accounts not paid within 30 days of the date of the invoice are subject to a 1.5% finance charge. Phone # (954) 568-9663 Fax # TBD pccontrolsinc@bellsouth.net Total Due Subtotal Sales Tax (0.0%) Unit DescriptionQuantity Price Each AmountService Date Hours - Contract Technician6 69.00 414.005/22/2023 Hours2 - Contract Technician 26 35.00 210.00 Troubleshoot Storm Water pump at Meadow Brook pump station. Pump shuts down on pressure alarm as soon as pump is started. Check pressure transmitter 4-20 mA output. Transmitter is bad and reads more than 20 mA. Simulate to pressure display and it is also bad and needs replaced. Disconnect alarm wiring and try to run but found floats to be terminated incorrectly. Correct float wiring and test. Station will now run, but still needs pressure transmitter and display replaced. Connect pump #1 at Lift Station #14. Test and leave pump in Off position. Pump is ready to install in Station. Lot Material - misc1 10.00 10.00 Fuel Surcharge - ... Broward and other1 10.00 10.00 $644.00 $644.00 $0.00