Hours2 - Contract Technician 26 35.00 210.00
Troubleshoot Storm Water pump at Meadow
Brook pump station. Pump shuts down on
pressure alarm as soon as pump is started.
Check pressure transmitter 4-20 mA output.
Transmitter is bad and reads more than 20 mA.
Simulate to pressure display and it is also bad
and needs replaced. Disconnect alarm wiring
and try to run but found floats to be terminated
incorrectly. Correct float wiring and test.
Station will now run, but still needs pressure
transmitter and display replaced. Connect
pump #1 at Lift Station #14. Test and leave
pump in Off position. Pump is ready to install in
Station.