HomeMy WebLinkAboutInv# PCI221561 - PC CONTROLS, INC - 06/09/2023Invoice Date 6/9/2023 Invoice # PCI221561 Bill To City of Dania Beach Accounts Payable 100 West Dania Beach Blvd Dania Beach, FL 33004 Service Location Darren Green Maintenance - Lift stations PC Controls Inc 4114 W. Palm Aire Drive #141B Pompano Beach, FL 33069 P.O. Number 230157 Terms Net 30 Due Date 7/9/2023 Technician PC/DE Comments Phone # (954) 568-9663 Fax # TBD pccontrolsinc@bellsouth.net Total Due Subtotal Sales Tax (0.0%) Unit DescriptionQuantity Price Each AmountService Date Hours - Contract Technician3 69.00 207.006/9/2023 Hours2 - Contract Technician 23 35.00 105.00 Liftstation 5 - Troubleshoot thermals for Pump 2 and found that the thermal switch in motor are either bad or normally opened. We then bypassed the thermals at operations request. Also found loose neutral wire at alarm horn, once terminated the pump ran fine and was returned to service. After this we Megged Pump 1 and noticed it Megged low - we disconnected pump in terminal box for repair. Fuel Surcharge - ... Broward and other1 10.00 10.00 $322.00 $322.00 $0.00