Unit DescriptionQuantity Price Each AmountService Date
Hours - Contract 2... Technician5 67.00 335.006/22/2023
Delivered to site three (3) FT440 flowmeter
head replacements. Install 1 new FT440 on
East Supernate flowmeter. Program, calibrate
and certify. Troubleshoot proximity switch for
Slaker feed belt. Clean switch and belt feed
wheel - Indicator goes Off and On but proximity
switch contacts don't open and close. Proximity
switch needs replaced.
Xmtr Fee - Contract Transmitter Certification Fee1 49.00 49.00
Fuel Surcharge - ... Broward and other1 10.00 10.00
$394.00
$394.00
$0.00
PC
CONTROLS
Ir--.JC::,
P.C. Controls Inc
4 t 14 W Palm Aire Dr 141 B , Pompano Beach, FL 33069
Phone: (954) 568-9663 , Fax: TBD
E-mail: pccontrolsinc@ bellsouth.net
Certified Flow Meter Test Record
Customer: City of Dania Beach
Consumptive Use Permit # 06-00187-W
Test Site East Supernatent Flow Transmitter, FIT-123 District ID# ___ _
Contact Nate Costa Number 954 924-3616
Meter Model Seametrics FT440E Serial# 06230382
Meter Accessories: None
Pipe Information at test site
Material PVC Schedule 40
Outside Diameter 2.375" OD Pipe Thickness .154" WT
Transducer Spacing 0 .55" Z-Mount Distance from Meter installation is 10 feet
Test Information using Fuji Porta-Flow Portable Ultrasonic Flowmeter
Test performed @ __ 47.2 ______ GPM
Initial Meter Reading at Calibration Start: 0 XI ---End: 400 X 1 ----
400 Gallons Totalized in 505 Seconds Average_ 4 7 .5_ GPM ----
Test Meter Reading at Calibration Start: 0 X I ---End : 400 X 1 ----
400 ____ Galtons Totalized in 508 Seconds Average _ 47.2_ GPM
Meter Tested at _100.6_ % Accuracy Last Meter Test 7 /22 Last Accuracy_l00.4%_
Comments : New Meter replacement haed. Prior to calibration meter was reading 100.6% of test meter -
Site meter read 47.5 GPM and test meter read 47.2 GPM.
Performed By: NP Conaway Date: 6 /22/23
Thi s is to certify that the above li sted equipment has been calibrated and me ets or exceed s all published specification s.
Calibration was performed using standards and /or instrumentation who se accurac y is traceable to the N.l.S .T .
Signature