HomeMy WebLinkAboutInv# PCI221599 - PC CONTROLS, INC - 07/19/2023Invoice
Date
7/19/2023
Invoice #
PCI221599
Bill To
City of Dania Beach
Accounts Payable
100 West Dania Beach Blvd
Dania Beach, FL 33004
Service Location
Darren Green
Maintenance - Lift stations
PC Controls Inc
4114 W. Palm Aire Drive #141B
Pompano Beach, FL 33069
P.O. Number
230157
Terms
Net 30
Due Date
8/18/2023
Technician
PC/DE
Comments
PC/MJ
Accounts not paid within 30 days of the date of the
invoice are subject to a 1.5% finance charge.
Phone # (954) 568-9663
Fax # TBD
pccontrolsinc@bellsouth.net
Total Due
Subtotal
Sales Tax (0.0%)
Unit DescriptionQuantity Price Each AmountService Date
Hours - Contract Technician3 69.00 207.007/17/2023
Hours2 - Contract Technician 23 35.00 105.00
Troubleshoot Lead, Lag, and OFF floats at "IT
Park" Liftstation and found that the OFF float
was defective and needs to be replaced. To
return tomorrow with float.
Hours - Contract Technician7 69.00 483.007/18/2023
Hours2 - Contract Technician 27 35.00 245.00
Page 1
Invoice
Date
7/19/2023
Invoice #
PCI221599
Bill To
City of Dania Beach
Accounts Payable
100 West Dania Beach Blvd
Dania Beach, FL 33004
Service Location
Darren Green
Maintenance - Lift stations
PC Controls Inc
4114 W. Palm Aire Drive #141B
Pompano Beach, FL 33069
P.O. Number
230157
Terms
Net 30
Due Date
8/18/2023
Technician
PC/DE
Comments
PC/MJ
Accounts not paid within 30 days of the date of the
invoice are subject to a 1.5% finance charge.
Phone # (954) 568-9663
Fax # TBD
pccontrolsinc@bellsouth.net
Total Due
Subtotal
Sales Tax (0.0%)
Unit DescriptionQuantity Price Each AmountService Date
Visited Liftstation 11 - operations state that it
occasionally does not turn off. On arrival level
was 2.9 feet so it had recently pumped and
turned off. Wait for level to reach 3.5 observe
Station coming on and shutting off at set point
2.1. Visit Liftstation #9 - operations state that
pump occasionally does not shut off. On arrival
station had a fault for phase failure, reset fault
and wait for level to rise to bring pump on as
water began to rise we see that we have a
backup activated light before pump comes on
we see that station has been running on back
up probe rather than submersible level
transmitter. Remove backup probe from Wet
Well and clean - adjust level of backup probe
so that it will be activated after Lead pump set
point. Now system will run on submersible level
transmitter - diagnosis pump most likely kept
running because of dirty backup probe. Visit IT
Park Liftstation and replace OFF float
(customer provided - test flow sequence and
put into service. Return to Liftstation 11 - upon
arrival level was at 2.9 wait for water to rise to
ON set point of 3.5 - pumped down and shut off
at OFF set point 2.1 station has been working
correctly all day.
Lot Material - misc1 5.00 5.00
Page 2
Invoice
Date
7/19/2023
Invoice #
PCI221599
Bill To
City of Dania Beach
Accounts Payable
100 West Dania Beach Blvd
Dania Beach, FL 33004
Service Location
Darren Green
Maintenance - Lift stations
PC Controls Inc
4114 W. Palm Aire Drive #141B
Pompano Beach, FL 33069
P.O. Number
230157
Terms
Net 30
Due Date
8/18/2023
Technician
PC/DE
Comments
PC/MJ
Accounts not paid within 30 days of the date of the
invoice are subject to a 1.5% finance charge.
Phone # (954) 568-9663
Fax # TBD
pccontrolsinc@bellsouth.net
Total Due
Subtotal
Sales Tax (0.0%)
Unit DescriptionQuantity Price Each AmountService Date
Fuel Surcharge - ... Broward and other2 10.00 20.00
Page 3
$1,065.00
$1,065.00
$0.00