Loading...
HomeMy WebLinkAboutInv# PCI221636 - PC CONTROLS, INC - 08/30/2023Invoice Date 8/30/2023 Invoice # PCI221636 Bill To City of Dania Beach Accounts Payable 100 West Dania Beach Blvd Dania Beach, FL 33004 Service Location Water Treatment Plant Nate Costa PC Controls Inc 4114 W. Palm Aire Drive #141B Pompano Beach, FL 33069 P.O. Number 230157 Terms Net 30 Due Date 9/29/2023 Technician PC/MJ Comments Accounts not paid within 30 days of the date of the invoice are subject to a 1.5% finance charge. Phone # (954) 568-9663 Fax # TBD pccontrolsinc@bellsouth.net Total Due Subtotal Sales Tax (0.0%) Unit DescriptionQuantity Price Each AmountService Date Hours - Contract Technician8 69.00 552.008/16/2023 Troubleshoot Filter #4 drain valve - remove a Lavender actuator, exercise valve, close valve manually - test to make sure Filter is not draining. Reinstall valve actuator, removed coupler so valve can not be accidentally opened. Troubleshoot Supernate - pump runs but the RUN status is not seen on HMI. Check contacts in motor starter they are ok. Troubleshoot PLC - digital input does not change status when pump is turned off and on. Calibrate and certify Distribution pressure and Distribution flow. Hours - Contract Technician8 69.00 552.008/18/2023 Calibrate and certify Influent to Membrane flowmeter and East Supernatant flow transmitter. Calibrate and certify Train 1 Concentrate Flow and Train 2 Concentrate flow meters. Fuel Surcharge - ... Broward and other2 10.00 20.00 $1,124.00 $1,124.00 $0.00