Loading...
HomeMy WebLinkAboutInv# PCI221744 - PC CONTROLS, INC - 12/07/2023Invoice Date 12/7/2023 Invoice # PCI221744 Bill To City of Dania Beach Accounts Payable 100 West Dania Beach Blvd Dania Beach, FL 33004 Service Location Water Treatment Plant Nate Costa PC Controls Inc 4114 W. Palm Aire Drive #141B Pompano Beach, FL 33069 P.O. Number 2024-00000010 Terms Net 30 Due Date 1/6/2024 Technician PC Comments Accounts not paid within 30 days of the date of the invoice are subject to a 1.5% finance charge. Phone # (954) 568-9663 Fax # TBD pccontrolsinc@bellsouth.net Total Due Subtotal Sales Tax (0.0%) Unit DescriptionQuantity Price Each AmountService Date Hours - Contract Technician6.5 69.00 448.5012/4/2023 Troubleshoot High Service Pump #5. Disconnect motor from VFD and Meg. Motor Megs bad. Run VFD with motor disconnected. VFD runs fine with no load. Disconnect motor from junction box on motor. Meg motor - motor Megs bad but wire Megs fine. Run new Carflex with new wire from j-box. There is no voltage on any of the wires that were disconnected from original actuator - to return later to further troubleshoot. Go to city electric to get 1" x 1/2" reducing bushing for valve actuator. Lot Material - 72' #14 Wire, Carflex 90 connectors and other related items. 1 33.72 33.72 Fuel Surcharge - ... Broward and other1 10.00 10.00 $492.22 $492.22 $0.00