HomeMy WebLinkAboutInv# PCI221744 - PC CONTROLS, INC - 12/07/2023Invoice
Date
12/7/2023
Invoice #
PCI221744
Bill To
City of Dania Beach
Accounts Payable
100 West Dania Beach Blvd
Dania Beach, FL 33004
Service Location
Water Treatment Plant
Nate Costa
PC Controls Inc
4114 W. Palm Aire Drive #141B
Pompano Beach, FL 33069
P.O. Number
2024-00000010
Terms
Net 30
Due Date
1/6/2024
Technician
PC
Comments
Accounts not paid within 30 days of the date of the
invoice are subject to a 1.5% finance charge.
Phone # (954) 568-9663
Fax # TBD
pccontrolsinc@bellsouth.net
Total Due
Subtotal
Sales Tax (0.0%)
Unit DescriptionQuantity Price Each AmountService Date
Hours - Contract Technician6.5 69.00 448.5012/4/2023
Troubleshoot High Service Pump #5.
Disconnect motor from VFD and Meg. Motor
Megs bad. Run VFD with motor disconnected.
VFD runs fine with no load. Disconnect motor
from junction box on motor. Meg motor - motor
Megs bad but wire Megs fine. Run new Carflex
with new wire from j-box. There is no voltage
on any of the wires that were disconnected from
original actuator - to return later to further
troubleshoot. Go to city electric to get 1" x 1/2"
reducing bushing for valve actuator.
Lot Material - 72' #14 Wire, Carflex 90 connectors
and other related items.
1 33.72 33.72
Fuel Surcharge - ... Broward and other1 10.00 10.00
$492.22
$492.22
$0.00