HomeMy WebLinkAboutInv# PCI221777 - PC CONTROLS, INC - 01/29/2024Invoice Date 1/29/2024 Invoice # PCI221777 Bill To City of Dania Beach Accounts Payable 100 West Dania Beach Blvd Dania Beach, FL 33004 Service Location Water Treatment Plant Nate Costa PC Controls Inc 4114 W. Palm Aire Drive #141B Pompano Beach, FL 33069 P.O. Number 2024-00000010 Terms Net 30 Due Date 2/28/2024 Technician PC Comments JES Accounts not paid within 30 days of the date of the invoice are subject to a 1.5% finance charge. Phone # (954) 568-9663 Fax # TBD pccontrolsinc@bellsouth.net Total Due Subtotal Sales Tax (0.0%) Unit DescriptionQuantity Price Each AmountService Date Hours - Contract Technician6 69.00 414.001/27/2024 Hours2 - Contract Technician 26 35.00 210.00 Disconnect Filter #2 Selector Switches and Indicator lights and record terminal strip designations. Remove existing starboard to use as a template. Troubleshoot High Service Pump 4 VFD. Control panel has lost control voltage. There is no voltage on wire 4201. Check fuses and transformer for 120 VAC. All fuses tested good and transformer has 120 VAC output and transformer fuse is good. Fuel Surcharge - ... Broward and other1 10.00 10.00 $634.00 $634.00 $0.00