Hours - Contract Technician3 69.00 207.004/5/2024
Troubleshoot Effluent Valve actuator for Filter
#2. Valve actuator works in HAND but not
AUTO. Found OFF-delay relay and Control
relay missing - install new OFF-delay relay and
Control relay. Valve actuator now works in
AUTO, indicator lights do not light up because
of missing wires on bulbs. To return with new
Indicating Lights - old lights are brittle and
breaking.
Hours - Contract Technician3 69.00 207.004/6/2024
Hours2 - Contract Technician 23 35.00 105.00
Install new Indicating Lights for Filter #2 Effluent
Valve actuator. Troubleshoot indicating lights
when valve actuator is fully open - voltage is on
both Indicating lights. Found problem with
neutral on indicating lights - correct problem,
test and put into service.
Each Relay. DPDT, 120 VAC with test, LED, 8-pin -
AAE
1 26.00 26.00
Each Indicating Light, IDEC, 120VAC (1 red/1 green)
- same as original lights.
2 37.11 74.22
Lot Material #14 wire, tape, cable ties and other
related items
1 10.00 10.00
Fuel Surcharge - ... Broward and other2 10.00 20.00