HomeMy WebLinkAboutInv# PCI221892 - PC CONTROLS, INC - 06/20/2024Invoice Date 6/20/2024 Invoice # PCI221892 Bill To City of Dania Beach Accounts Payable 100 West Dania Beach Blvd Dania Beach, FL 33004 Service Location Water Treatment Plant Nate Costa PC Controls Inc 4114 W. Palm Aire Drive #141B Pompano Beach, FL 33069 P.O. Number 2024-00000010 Terms Net 30 Due Date 7/20/2024 Technician PC Comments Accounts not paid within 30 days of the date of the invoice are subject to a 1.5% finance charge. Phone # (954) 568-9663 Fax # TBD pccontrolsinc@bellsouth.net Total Due Subtotal Sales Tax (0.0%) Unit DescriptionQuantity Price Each AmountService Date Hours - Contract Technician8 69.00 552.006/14/2024 Troubleshoot High Service Pumps #2 and #3. Both VFD's error code was for overvoltage. Disconnect motors at the VFD. Meg motors from VFD both appear to be shorted to ground. Power up VFD's and run in HAND with no load, VFD's appear to be ok. Disconnect motors at the motor. Meg motor and still show both pump motors shorted to ground. Disconnect and prepare for removal and repair. Troubleshoot Filter # 1 Effluent valve. Valve opens in AUTO but will not close automatically. Check operation of floats. Check operation of electrical timing relay. Found bad Timing Relay on lower float. Replace and check operation several times and put filter into service. Lot Material - Misc1 10.00 10.00 Fuel Surcharge - ... Broward and other1 10.00 10.00 $572.00 $572.00 $0.00