Unit DescriptionQuantity Price Each AmountService Date
Hours - Contract Technician8 69.00 552.006/14/2024
Troubleshoot High Service Pumps #2 and #3.
Both VFD's error code was for overvoltage.
Disconnect motors at the VFD. Meg motors
from VFD both appear to be shorted to ground.
Power up VFD's and run in HAND with no load,
VFD's appear to be ok. Disconnect motors at
the motor. Meg motor and still show both pump
motors shorted to ground. Disconnect and
prepare for removal and repair. Troubleshoot
Filter # 1 Effluent valve. Valve opens in AUTO
but will not close automatically. Check
operation of floats. Check operation of
electrical timing relay. Found bad Timing Relay
on lower float. Replace and check operation
several times and put filter into service.