HomeMy WebLinkAboutInv# PCI221909 - PC CONTROLS, INC - 07/09/2024Invoice
Date
7/9/2024
Invoice #
PCI221909
Bill To
City of Dania Beach
Accounts Payable
100 West Dania Beach Blvd
Dania Beach, FL 33004
Service Location
Darren Green
Maintenance - Lift stations
PC Controls Inc
4114 W. Palm Aire Drive #141B
Pompano Beach, FL 33069
P.O. Number Terms
Net 30
Due Date
8/8/2024
Technician
PC
Comments
Accounts not paid within 30 days of the date of the
invoice are subject to a 1.5% finance charge.
Phone # (954) 568-9663
Fax # TBD
pccontrolsinc@bellsouth.net
Total Due
Subtotal
Sales Tax (0.0%)
Unit DescriptionQuantity Price Each AmountService Date
Hours - Contract Technician8 69.00 552.007/3/2024
Disconnect Thermals for Pump #3 at Lift Station
7 as per Darren Greens direction Test pump.
Motor starter comes on but pump does not lift
check valve. Reverse rotation of pump #3. Test
operation and put into service. Troubleshoot
soft starts at Lift Station 16. Pump #1 and #2
were tripped, Pump 1 had an error that was
phase or voltage unbalance. When checking
voltage 1- phase read low 258 VAC and
1-phase read high315 VAC. All 3 should be
within 10 VAC of 277 VAC. Through process of
elimination it was found that the voltage
imbalance was caused by the Soft Start for
Pump #2. To give quote for soft start
replacement cost. Set level controller at Lift
Station 11 for pumps to come on at 4.5 feet
instead of 3.5 to bring down the number of
starts and stops per day. Time station - it takes
19 minutes for pump to come on then pump
runs about 4 1/2 minutes before shutting off.
Fuel Surcharge - ... Broward and other1 10.00 10.00
$562.00
$562.00
$0.00