HomeMy WebLinkAboutInv# PCI221909 - PC CONTROLS, INC - 07/09/2024Invoice Date 7/9/2024 Invoice # PCI221909 Bill To City of Dania Beach Accounts Payable 100 West Dania Beach Blvd Dania Beach, FL 33004 Service Location Darren Green Maintenance - Lift stations PC Controls Inc 4114 W. Palm Aire Drive #141B Pompano Beach, FL 33069 P.O. Number Terms Net 30 Due Date 8/8/2024 Technician PC Comments Accounts not paid within 30 days of the date of the invoice are subject to a 1.5% finance charge. Phone # (954) 568-9663 Fax # TBD pccontrolsinc@bellsouth.net Total Due Subtotal Sales Tax (0.0%) Unit DescriptionQuantity Price Each AmountService Date Hours - Contract Technician8 69.00 552.007/3/2024 Disconnect Thermals for Pump #3 at Lift Station 7 as per Darren Greens direction Test pump. Motor starter comes on but pump does not lift check valve. Reverse rotation of pump #3. Test operation and put into service. Troubleshoot soft starts at Lift Station 16. Pump #1 and #2 were tripped, Pump 1 had an error that was phase or voltage unbalance. When checking voltage 1- phase read low 258 VAC and 1-phase read high315 VAC. All 3 should be within 10 VAC of 277 VAC. Through process of elimination it was found that the voltage imbalance was caused by the Soft Start for Pump #2. To give quote for soft start replacement cost. Set level controller at Lift Station 11 for pumps to come on at 4.5 feet instead of 3.5 to bring down the number of starts and stops per day. Time station - it takes 19 minutes for pump to come on then pump runs about 4 1/2 minutes before shutting off. Fuel Surcharge - ... Broward and other1 10.00 10.00 $562.00 $562.00 $0.00