Loading...
HomeMy WebLinkAboutInv# PCI221929 - PC CONTROLS, INC - 08/13/2024Invoice Date 8/13/2024 Invoice # PCI221929 Bill To City of Dania Beach Accounts Payable 100 West Dania Beach Blvd Dania Beach, FL 33004 Service Location Water Treatment Plant Nate Costa PC Controls Inc 4114 W. Palm Aire Drive #141B Pompano Beach, FL 33069 P.O. Number 2024-00000010 Terms Net 30 Due Date 9/12/2024 Technician PC Comments Accounts not paid within 30 days of the date of the invoice are subject to a 1.5% finance charge. Phone # (954) 568-9663 Fax # TBD pccontrolsinc@bellsouth.net Total Due Subtotal Sales Tax (0.0%) Unit DescriptionQuantity Price Each AmountService Date Hours - Contract Technician8 69.00 552.008/9/2024 Troubleshoot West unit Influent flowmeter. Meter output is high and does not reflect actual flow. Found that the flowmeter has a bad output and reads 4.57 mA at zero. Install new flowmeter transmitter - test, calibrate and put into service. Deliver to site 5 ATDR-6 fuses for SKID valve actuator and 1 FT-440 serial #11232800. Each Seametrics FT440W-126 Loop Powered, Dual Scaled Pulse and 4-20 mA output, Wall Mount with hinged display cover. 1 976.40 976.40 Each Fuse, ATDR, 6A, Class CC5 21.66 108.30 Fuel Surcharge - ... Broward and other1 10.00 10.00 $1,646.70 $1,646.70 $0.00