Unit DescriptionQuantity Price Each AmountService Date
Hours - Contract Technician8 69.00 552.008/9/2024
Troubleshoot West unit Influent flowmeter.
Meter output is high and does not reflect actual
flow. Found that the flowmeter has a bad
output and reads 4.57 mA at zero. Install new
flowmeter transmitter - test, calibrate and put
into service. Deliver to site 5 ATDR-6 fuses for
SKID valve actuator and 1 FT-440 serial
#11232800.
Each Seametrics FT440W-126 Loop Powered, Dual
Scaled Pulse and 4-20 mA output, Wall Mount
with hinged display cover.
1 976.40 976.40
Each Fuse, ATDR, 6A, Class CC5 21.66 108.30
Fuel Surcharge - ... Broward and other1 10.00 10.00