HomeMy WebLinkAboutInv# PCI221934 - PC CONTROLS, INC - 08/22/2024Invoice Date 8/22/2024 Invoice # PCI221934 Bill To City of Dania Beach Accounts Payable 100 West Dania Beach Blvd Dania Beach, FL 33004 Service Location Water Treatment Plant Nate Costa PC Controls Inc 4114 W. Palm Aire Drive #141B Pompano Beach, FL 33069 P.O. Number 2024-00000010 Terms Net 30 Due Date 9/21/2024 Technician PC Comments Accounts not paid within 30 days of the date of the invoice are subject to a 1.5% finance charge. Phone # (954) 568-9663 Fax # TBD pccontrolsinc@bellsouth.net Total Due Subtotal Sales Tax (0.0%) Unit DescriptionQuantity Price Each AmountService Date Hours - Contract Technician8 69.00 552.008/20/2024 Troubleshoot train 2 Feed Water valve actuator. Actuator blows fuse randomly, but recently is more frequent. Inspect actuator. Disconnect actuator and meg the wire for 3-phase. L1 and L2 both have resistance ground and each other. Pull new wire, terminate and test actuator - put into service. Lot Material - Wire (200' #12 THHN) and other items needed to complete the work. 1 55.00 55.00 Fuel Surcharge - ... Broward and other1 10.00 10.00 $617.00 $617.00 $0.00