Hours - Contract Technician8 69.00 552.008/20/2024
Troubleshoot train 2 Feed Water valve actuator.
Actuator blows fuse randomly, but recently is
more frequent. Inspect actuator. Disconnect
actuator and meg the wire for 3-phase. L1 and
L2 both have resistance ground and each other.
Pull new wire, terminate and test actuator - put
into service.
Lot Material - Wire (200' #12 THHN) and other
items needed to complete the work.
1 55.00 55.00
Fuel Surcharge - ... Broward and other1 10.00 10.00