Unit DescriptionQuantity Price Each AmountService Date
Hours - Contract Technician8 69.00 552.008/16/2024
Troubleshoot High Service Pump #5. VFD had
an overvoltage error. Reset pump by powering
VFD down then turning it back on. Test in
local/hand and VFD fails immediately.
Disconnect motor at the VFD. Reset VFD then
test in hand/local VFD runs with motor
disconnected. Output is good checking each
phase to ground and phase to phase. VFD is
most likely good. Meg motor from disconnect.
Motor megs bad, wire megs good. Disconnect
High Service Pump. #5 at the pump. Checking
for signs of water intrusion. No water was
visible when opened. Meg motor, motor is
shorted to ground. Disconnect J-box from
pump for repair. Troubleshoot SKID #2 Raw
Water valve actuator. Cycled the valve 8 times
open and close. Actuator never failed.
Amperage on actuator was .53-.54 amp on
every phase every time. Install new motor and
brake on Filter #1 influent valve actuator.
Lot Material - misc for repairs1 20.00 20.00
Fuel Surcharge - ... Broward and other1 10.00 10.00
$582.00
$582.00
$0.00