HomeMy WebLinkAboutInv# PCI221931 - PC CONTROLS, INC - 08/19/2024 (2)Invoice Date 8/19/2024 Invoice # PCI221931 Bill To City of Dania Beach Accounts Payable 100 West Dania Beach Blvd Dania Beach, FL 33004 Service Location Water Treatment Plant Nate Costa PC Controls Inc 4114 W. Palm Aire Drive #141B Pompano Beach, FL 33069 P.O. Number 2024-00000010 Terms Net 30 Due Date 9/18/2024 Technician PC Comments Phone # (954) 568-9663 Fax # TBD pccontrolsinc@bellsouth.net Total Due Subtotal Sales Tax (0.0%) Unit DescriptionQuantity Price Each AmountService Date Hours - Contract Technician8 69.00 552.008/16/2024 Troubleshoot High Service Pump #5. VFD had an overvoltage error. Reset pump by powering VFD down then turning it back on. Test in local/hand and VFD fails immediately. Disconnect motor at the VFD. Reset VFD then test in hand/local VFD runs with motor disconnected. Output is good checking each phase to ground and phase to phase. VFD is most likely good. Meg motor from disconnect. Motor megs bad, wire megs good. Disconnect High Service Pump. #5 at the pump. Checking for signs of water intrusion. No water was visible when opened. Meg motor, motor is shorted to ground. Disconnect J-box from pump for repair. Troubleshoot SKID #2 Raw Water valve actuator. Cycled the valve 8 times open and close. Actuator never failed. Amperage on actuator was .53-.54 amp on every phase every time. Install new motor and brake on Filter #1 influent valve actuator. Lot Material - misc for repairs1 20.00 20.00 Fuel Surcharge - ... Broward and other1 10.00 10.00 $582.00 $582.00 $0.00