Unit DescriptionQuantity Price Each AmountService Date
Hours - Contract Technician8 69.00 552.0010/28/2024
Troubleshoot floats and level control for Effluent
valves on Filters 1 and 2. Filter 2 had a loose
wire and was returned to AUTOmatic control.
Filter 1 began working again when filter Effluent
valve was placed in AUTO. Install new
Ultrasonic Level transmitters on Filter 2 but it
still doesn't work. Remove and take to shop to
further troubleshoot.
Hours - Contract Technician8 69.00 552.0011/6/2024
Install new Flowline Echopod Ultrasonic Level
transmitter on Filter #2. Remove old float
system and install stilling Well, mount 24 VDC
power supply and (1) 24 VDC 8-pin Control
Relay for Filter # 2 effluent valve. Terminate
120 VAC and effluent valve relay coil in old filter
panel. Test and put into service.